The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.
|
Parameter |
Designation |
See |
|
5.10 |
Calling up the parameter level |
|
|
5.11 |
Activating the LIS-SV for the ABULiner |
|
|
5.11 |
Setting the gear ratio |
|
|
5.12 |
Activating double lifting speed |
|
|
5.14 |
Setting the run-on time of the auxiliary fan |
|
|
Danger during setting work! During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things. This means the wire rope hoist cannot be monitored for excess load, among other things. This in turn means the load could fall and kill or injure people! Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes! |
All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.
|
|
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Open the menu of the
LIS-SV. See the documentation “Load indicator system LIS-SV”.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.10.
Press ENTER.
● The 'ABULiner' parameter level is activated.
● Parameter 5.11 is displayed.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.99.
Press ENTER.
● The previous parameter level is reactivated.
● Parameter 5.10 is displayed.
The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.
In the ABULiner mode (a value is set for parameter 5.11):
─ The LIS-SV can monitor the total load for a maximum of two wire rope hoists.
─ Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.
─ A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV cannot be used.
─ Parameter 4.5 (setting for load-controlled switching point) is not available.
In the normal mode (no value is set for parameter 5.11):
─ Operation of the ABULiner Lifting/Lowering unit is not possible.
─ The LIS-SV can monitor the total load for up to three wire rope hoists.
─ Input F3 serves in measuring the load of a third wire rope hoist.
─ A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV can be used.
─ Parameter 4.5 (setting for load-controlled switching point) can be used.
The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.
|
| |
|
Cable speed |
|
Read off the type
designation at the type plate of the wire rope hoist.
Read off the cable
speed.
From this table, select
the gear ratio that matches the cable speed.
|
Cable speed | |||||
|
Hoist motor GM |
32 m/min at 50 Hz |
25 m/min at 50 Hz |
20 m/min at 50 Hz |
16 m/min at 50 Hz | |
|
800.4 |
50.01 |
63.49 |
77.77 |
98.16 | |
|
800.5 |
47.03 |
60.04 |
74.66 |
95.03 | |
|
1000.6 |
54.43 |
68.91 |
84.00 |
105.1 | |
|
1000.7 |
54.60 |
68.06 |
81.45 |
104.6 | |
|
2000.3 |
58.22 |
74.23 |
91.19 |
118.4 | |
|
3000.4 |
73.61 |
93.92 |
118.4 |
152.9 | |
|
5000.3 |
85.14 |
109.3 |
132.8 |
169.0 | |
|
5000.4 |
80.20 |
104.9 |
127.7 |
160.6 | |
|
6000.3 |
94.69 |
118.5 |
149.6 |
182.7 | |
|
7000.1 |
118.0 |
148.3 |
182.6 |
232.0 | |
Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.11.
Press ENTER.
● The set value is displayed.
If the value is 0.00, the function is deactivated.
● Hold ENTER pressed.
● CODE is displayed.
Hold ENTER pressed.
|
| |
|
Enter button |
Arrow buttons |
Enter the code 1443.
Press ENTER briefly.
|
| |
|
Enter button |
Arrow buttons |
Set the value from the
table.
If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0. In this case, set the value to zero first.
Press ENTER briefly.
The third OVA, Pico & Coco & Chico , is the absolute final entry in the official animated series. No further animations were ever produced. Why People Searched for "OVA 3 2021"
The series remains out of print in most official capacities due to its controversial nature and aging production quality. Summary for Readers
In the early days of YouTube, reaction videos to the first episode of Boku no Pico became a viral genre of their own. Creators recorded their genuine shock and discomfort, cementing the anime as a rite of passage for internet subcultures. boku no pico ova 3 2021
Veteran anime fans often "recommend" the series to newcomers as a "wholesome, must-watch 2021 reboot" as a form of trolling.
It is a shota (young boy-centric) adult anime produced by Natural High . It was marketed as the first series specifically for this genre . The third OVA, Pico & Coco & Chico
Fast-forward to 2021, and Boku no Pico is experiencing a resurgence in popularity. The series has been rediscovered by a new generation of fans, who are drawn to its unique blend of psychological complexity and atmospheric tension. The 2021 revival includes a re-release of the original series, as well as new OVAs and adaptations.
, it is important to clarify that . The original series concluded well over a decade ago, and current "news" regarding a 2021 release is typically the result of internet memes or misinformation. Summary for Readers In the early days of
So, why is OVA 3 such an important part of the Boku no Pico franchise, particularly in the context of the 2021 revival? The answer lies in its exploration of themes that are just as relevant today as they were when the episode was first released. Pico's struggles with identity, trauma, and relationships continue to resonate with audiences, and OVA 3 provides a powerful and thought-provoking examination of these issues.
Unlike standard continuous anime episodes, this OVA explicitly segments its runtime (e.g., "Chapter 1: The Secret," "Chapter 2: The Meeting," etc.). This structural choice serves a specific function:
The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.14.
Press ENTER.
● The set value is displayed.
|
| |
|
Enter button |
|
Set the value to between 3
and 10 minutes using the arrow buttons.
Press ENTER.